Products Features:
7-inch touch control screen | |
Power Range: | 10-200KVA (PF=0.8) (3/3) |
Battery voltage: | 192/360/384vdc |
Input voltage: | 208/220/380/400/415Vac (Three phase) |
Output voltage: | 208/220/380/400/415Vac (Three phase) |
Wifi module monitor(Option) |
Products Parameters
CP10K----CP200K(Three-ins and Three outs) | ||||||||||||
Model | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 50KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA |
Capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 40KW | 48KW | 64KW | 80KW | 96KW | 128KW | 160KW |
Battery Voltage | 384V | 396V | ||||||||||
UPS effciency | 80% | |||||||||||
Noise level | 48~54dB(Distance 1m) | 53~60dB( Distance 1m) | 53~62dB(Distance 1m) | 54~65dB( Distance 1m) | ||||||||
Size(W×D×Hmm) | 730X460X1180 | 700X550X1120 | 790X660X1550 | 1100X900X1520 | 1300X900X1780 | |||||||
Weight(Kg)(Excluding battery) | 200 | 235 | 260 | 315 | 335 | 470 | 480 | 560 | 730 | 870 | 1160 | 1210 |
Input | Voltage | 3phases 4 wires and ground, 380V±25% | ||||||||||
Frequency | 50Hz/60Hz±5%(Automaticity) | |||||||||||
Power factor | 0.8 | |||||||||||
Inverter output | Voltage | 3phases 4 wires, 380V±1% | ||||||||||
Frequency | 50Hz/60Hz±0.05%(By Battery) | |||||||||||
Harmonic distortion | Linear Load<3%, Non-linear Load <5% | |||||||||||
Imbalance voltage | Balance load=1%,Imbalance load =3% | |||||||||||
Phase shif angle | Balance load=1%,Imbalance load =2 | |||||||||||
Transient response | Output at 0~50%~100%=5%, response=10ms | |||||||||||
Overload capacity | 110%≥300Min,125%≥10Min,150%≥1Min | |||||||||||
Crest Factor | 3:01 | |||||||||||
Wave Form | Pure sina wave | |||||||||||
Transfer time | 0ms | |||||||||||
Battery | Max.charging current | 30A | ||||||||||
Charging time (Standard) | 12hours | |||||||||||
Protective function | Input over-voltage, under-voltage; output overload, shortcircuit; Inver over-temperature; Battery under-voltage, over-voltage | |||||||||||
Running temperature & Humidity | 0-40 degree Celsius, Less than 95%(without condensing) | |||||||||||
Altitude | <1000m(with increase of 100m, it will reduce output of1%)max 4000m | |||||||||||
Communication interface | Rs232 | |||||||||||
Remote signaling | Dry contact (batterylow, battery discharging, bypass/fault),EPO | |||||||||||
Remote control | EPO and bypass | |||||||||||
Degree of Protection | IP20( front door opened) | |||||||||||
Parallel mode | N+1、N+X、can be in parallel with different power capacity | |||||||||||
Software interface | Windows9x、2000、NT、Me、XP、Linux、Novell、Macosx、NT4.0 | |||||||||||
Mean time between failures | 300,000 Hours | |||||||||||
Optional | Dustproof & dampproof, Isolating inverter transformer, lightning surge absorption, static switches, manual maintainence switch | |||||||||||
Display | 7 Inch Touch Screen System |